Beam example 2: trace a library-floor load into beam B3
← Read this lecture example beside its chapter concepts
Design the fully restrained supporting beam B3 in the library floor plan. Characteristic dead and imposed floor loads are and ; the dead load includes the self-weight allowances used by the example. Use S355 and the lecturer’s simply supported member model.
Original source: LectureNotes/Ch 3_Beam.pdf — p. 22, p. 23, p. 24, p. 25, p. 26.
A given value comes from the question or diagram.
A lookup value comes from the named table.
A calculated value follows from the working.
Each assumption is stated where the calculation needs it.
Known information, diagram labels and unknowns
A safe beam can still sag too far
Check whether the beam displacement exceeds the permitted service limit.
Prediction, then explanation. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.
Load bends each beam segment. The curvature accumulates along the span. Material stiffness E and geometric stiffness I resist that deformation.
Use w in N/mm, L in mm, E in N/mm² and I in mm⁴. The resulting midspan deflection is in mm.
Scope. The formula assumes a prismatic, simply supported, linear-elastic beam with full-span UDL. Use the stated service load and deflection limit.
Check and takeaway. A higher yield grade does not automatically increase E. Passing a strength check therefore does not prove acceptable deflection.
Follow one strip of floor
An area load must become a beam load before beam reactions can be calculated.
Prediction, then explanation. At fixed area load, twice the tributary width gives twice the line load. An end reaction remains a concentrated force.
Consider one metre along the beam. The associated floor area is b square metres. Multiply area load by that width.
q is area load in kN/m²; b is tributary width in m; w is line load in kN/m.
Scope. Determine b from slab spanning and supports. Add beam self-weight separately. A secondary-beam reaction is not automatically a UDL.
Check and takeaway. Illustration: . The width cancels one length unit.
Apply the reasoning to this section’s data and conditions
| Feature | Meaning for loading |
|---|---|
| Slab span marks crossing the B1 lines | Slab load reaches the parallel B1 beams over a tributary width. |
| B1 above and below each interior B2 | Each B2 loading point receives two B1 end reactions. |
| B2 on both sides of the interior B3 | B3 receives two B2 end reactions at its centre. |
| B3 also directly borders slab strips | Interior B3 carries its own tributary slab strip, represented as a UDL. |
| Given and assumed | All self-weight is already allowed for in the supplied dead intensity. B3 fully restrained; lecturer assumes brittle finishes for serviceability. |
Why this method applies
Balance the isolated beam
Find the two vertical reactions before calculating internal shear or moment.
Prediction, then explanation. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.
Take moments about A. Reaction A has zero lever arm there. Then use vertical force balance to find reaction A.
P, RA and RB are forces in kN. L is support spacing and a is load position, both in m.
Scope. These expressions describe one point load on a simply supported beam. Add other loads through equilibrium; keep their actual positions.
Check and takeaway. Illustration: P = 60 kN, L = 6 m and a = 2 m give RB = 20 kN and RA = 40 kN.
Apply the reasoning to this section’s data and conditions
Work upstream before downstream: slab → B1 → B2 → B3.
A supporting beam receives a point load equal to the end reaction of the supported beam, not that beam’s entire load.
Keep dead and imposed reactions separate until the B3 loading is established.
Do not treat the horizontal bay width as the B3 span.
1. Slab to B1
Use the same mechanism: Follow one strip of floor. At fixed area load, twice the tributary width gives twice the line load. An end reaction remains a concentrated force.
Use the same mechanism: Balance the isolated beam. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.
Apply the reasoning to this section’s data and conditions
The division by two comes from a uniformly loaded simply supported span.
These are characteristic reactions, before the ultimate factors.
Mechanism detailsFollow the floor load in 3D
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
The floor carries pressure in .
The highlighted strip belongs to one secondary beam.
Multiply pressure by tributary width: .
The illustration uses .
- A primary beam receives the secondary beam reaction at their connection, not a new full-span UDL.
Trace reactions down to columns and foundations.
Count each loaded area once.
2. B1 reactions to B2
Use the same mechanism: Follow one strip of floor. At fixed area load, twice the tributary width gives twice the line load. An end reaction remains a concentrated force.
Use the same mechanism: Balance the isolated beam. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.
Apply the reasoning to this section’s data and conditions
There are three internal point loads, not four: four slab strips are bounded by three interior B1 lines and the two B3 boundaries.
Symmetry of the three loads gives half the total at each B2 end.
Loads arriving directly at column-supported beam ends do not add span bending.
Mechanism detailsFollow the floor load in 3D
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
The floor carries pressure in .
The highlighted strip belongs to one secondary beam.
Multiply pressure by tributary width: .
The illustration uses .
- A primary beam receives the secondary beam reaction at their connection, not a new full-span UDL.
Trace reactions down to columns and foundations.
Count each loaded area once.
3. Assemble B3 point load and direct slab UDL
Use the same mechanism: Follow one strip of floor. At fixed area load, twice the tributary width gives twice the line load. An end reaction remains a concentrated force.
Keep load categories separate
A floor carries permanent material and changing occupancy loads. Find the design load for the stated check.
Prediction, then explanation. Increasing imposed load changes its own term. It does not change the dead-load factor or the steel stiffness.
First convert mass to weight where required. Next collect G and Q in compatible units. Apply the combination specified by the course problem.
G is characteristic dead load; Q is characteristic imposed load. Wu is the design load for this course gravity combination.
Scope. This combination is not universal. Use the specified service load for deflection and the stated factors for other standards or cases.
Check and takeaway. Illustration: G = 10 kN and Q = 5 kN give 22 kN. Factoring their sum by one guessed factor loses the distinction.
Apply the reasoning to this section’s data and conditions
Physical interpretation: How a floor load reaches a beam
Each beam collects the load from its own strip of floor.
Sketch, not to scale; use the original dimensions.
- Find the tributary width from the actual plan.
- Area load × tributary width gives load per beam length.
- A supporting beam receives the other beam’s end reaction.
Remember: A reaction becomes a point load, not automatically a UDL.
The factor of two at the central point represents the B2 on each side of B3.
It does not double B3’s span or its tributary strip.
Mechanism detailsFollow the floor load in 3D
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
The floor carries pressure in .
The highlighted strip belongs to one secondary beam.
Multiply pressure by tributary width: .
The illustration uses .
- A primary beam receives the secondary beam reaction at their connection, not a new full-span UDL.
Trace reactions down to columns and foundations.
Count each loaded area once.
4. Reactions, shear and moment of B3
Use the same mechanism: Balance the isolated beam. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.
A cut reveals the internal actions
Find where the beam moment is largest. A large load arrow alone does not locate that point.
Prediction, then explanation. Under a uniform downward load, shear falls steadily. Moment reaches a stationary value where shear becomes zero.
Balance the forces on the cut piece to get V. Balance their moments about the cut to get M. Evaluate each load region separately.
x and L use m; w uses kN/m; V uses kN; M uses kN·m. These lines apply before any point load.
Scope. A point load adds a shear jump. A concentrated couple adds a moment jump. Check load points, supports and overhang roots too.
Check and takeaway. A UDL gives a sloping shear line and a curved moment line. A flat moment diagram therefore cannot represent a loaded UDL region.
Apply the reasoning to this section’s data and conditions
Physical interpretation: Why reactions balance the loads
Think of a seesaw that must neither fall nor turn.
Sketch, not to scale; use the original dimensions.
- Upward and downward forces must balance.
- Take moments about a support to eliminate its reaction.
- Use perpendicular distance from the point to the force line.
Remember: A lateral restraint is not automatically a vertical support.
Mechanism detailsBalance reactions and moments
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
This demonstrator is a simply supported 6 m beam with a 60 kN point load.
It is not the page’s original loading diagram.
.
Moving the load towards B increases .
.
The two upward reactions must sum to P.
With the load at midspan, .
End couples, UDLs and overhangs require their own equilibrium terms.
5. Select UB
A table value has conditions
Find a design property without mixing a row, column or standard from a different case.
Prediction, then explanation. A different flange thickness can select a lower design strength even when the steel grade name remains unchanged.
Match the complete section designation. Read the relevant axis and unit. For strength tables, select material, thickness and curve before interpolating.
Given values come from the question. Lookup values come from a named table. Assumed values require an explicit condition.
Scope. A missing row or omitted restraint cannot be recovered from a schematic’s scale. Keep the result conditional when required data are absent.
Check and takeaway. Record the table, row, column and unit beside the substitution. That makes a later check possible.
Use the property for the physical question
A section table contains several numbers. Choose the property that matches the calculation and bending axis.
Prediction, then explanation. Moving equal area away from an axis increases I about that axis. It does not increase total area.
Each small area contributes its area multiplied by squared distance. Sum those contributions to obtain I.
I is second moment of area in mm⁴. y is distance from the chosen axis in mm. A is area in mm². r is radius of gyration in mm.
Scope. Z is elastic section modulus; S is plastic section modulus in this course. Neither is interchangeable with I.
Check and takeaway. A nominal section designation is a row identifier. Use the actual dimensions and units in that exact row.
Internal tension and compression resist moment
Find which section resistance applies before comparing it with the moment demand.
Prediction, then explanation. A larger appropriate section modulus raises resistance at fixed strength. Local plate buckling can restrict the usable modulus.
Classify the section first. At low shear, use the elastic expression for Class 3 or the prescribed capped plastic expression for Classes 1 and 2.
py uses N/mm². S is plastic modulus and Z is elastic modulus, both in mm³. Mc then uses N·mm.
Scope. This is section resistance, not whole-member LTB resistance. High shear and Class 4 require their appropriate treatment.
Check and takeaway. Selecting the larger of the two capped terms defeats the cap. Use their minimum.
Apply the reasoning to this section’s data and conditions
Data File p.9 row gives , , , , , and .
Page 10, the same designation, gives , , .
confirms pᵧ=355.
No interpolation is used for section properties: read the exact row.
Mechanism detailsRead a table without losing the keys
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
- Name the required property: material strength, section property, buckling strength or a moment factor.
- Keep section size, steel grade, thickness band, curve and axis as separate lookup keys.
, and require different conversion powers.
Do not use adjacent columns interchangeably.
Use bracketing rows within the same valid column.
The original page remains the source of all table values.
6. Classify the trial section
Find which plate buckles first
Before using plastic bending resistance, check whether the flange and web can sustain the required stress distribution.
Prediction, then explanation. At fixed width, a thinner plate has a larger width-to-thickness ratio. Local buckling then becomes more restrictive.
Calculate the flange and web ratios separately. Compare each with the limits for its stress condition. The worse class governs.
py is the design yield strength in N/mm². ε is a dimensionless scale used in the supplied classification limits.
Scope. Pure bending and uniform compression use different web limits. Class 2 allows plastic resistance but not the Class 1 rotation capability.
Check and takeaway. A Class 1 web and Class 2 flange give a Class 2 section. Do not average the class numbers.
Use the same mechanism: A table value has conditions. A different flange thickness can select a lower design strength even when the steel grade name remains unchanged.
Apply the reasoning to this section’s data and conditions
Mechanism detailsWhy thin elements buckle locally
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
- The flange outstand and web have different widths, thicknesses and edge support conditions.
- A thinner plate can wrinkle locally before the complete member loses stability.
Class 1 allows plastic rotation.
Class 2 reaches plastic resistance.
Class 3 reaches elastic resistance.
Class 4 requires effective properties.
Check every relevant compression element with the supplied limits and stress distribution.
The deformation shown is qualitative.
7. Check shear resistance
The web carries the shear check
Compare the applied shear with the resistance of the prescribed shear area.
Prediction, then explanation. At fixed design strength and depth, increasing web thickness increases this shear resistance.
Calculate the prescribed shear area. Multiply by the design shear stress from the course rule. Then compare matching force units.
D is overall depth; t is web thickness, in mm. Av uses mm². py uses N/mm², giving Vc in N.
Scope. Apply this area definition to the stated rolled section. Check web slenderness separately. The factor 0.6 is the low-shear threshold, not this resistance coefficient.
Check and takeaway. A shear pass alone does not prove bending, deflection or local support-web adequacy.
Apply the reasoning to this section’s data and conditions
Mechanism detailsSee shear in the web
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
- Internal shear keeps the two sides of the cut in vertical equilibrium.
For the course’s common I-section case, the web provides the principal shear area.
Use the specified definition.
- A slender web may require a different shear-buckling route before a simple shear-resistance formula is used.
Use where applicable in the course.
Convert N to kN before comparing with design shear.
8. Check moment resistance
Use the same mechanism: Internal tension and compression resist moment. A larger appropriate section modulus raises resistance at fixed strength. Local plate buckling can restrict the usable modulus.
Apply the reasoning to this section’s data and conditions
Physical interpretation: Why one flange squeezes and the other stretches
Bending makes opposite sides of the section do opposite jobs.
Sketch, not to scale; use the original dimensions.
- Find the moment from the actual loads and supports.
- Choose the resistance formula allowed by the section class.
- Check whether the coexistent shear changes that formula.
Remember: Use shear at the location being checked, not an unrelated maximum.
The source’s requested B3 design demonstrates shear, moment and deflection.
It does not specify a bearing geometry for a numerical local-web design here.
Do not import the bearing from Example 1.
Mechanism detailsCompression and tension across a section
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
- For sagging, the top flange is in compression and the bottom in tension; hogging reverses this.
- Elastic bending stress varies with distance from the neutral axis: .
- The section class governs whether elastic, plastic or effective properties may be used.
Use the shear at the section under examination.
The largest shear elsewhere is not automatically coexistent.
9. Check B3 serviceability
Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.
Apply the reasoning to this section’s data and conditions
Physical interpretation: How much does the beam sag?
Strength asks whether it fails; deflection asks how far it moves.
Sketch, not to scale; use the original dimensions.
- Use the serviceability load case specified by the course question.
- Choose the expression matching the support and load positions.
- Use consistent units for load, length, E and I.
Remember: The largest deflection is not always at midspan.
Mechanism detailsSee stiffness and deflection
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
Use the specified SLS load, span and support arrangement.
The demonstrator has a full-span UDL.
The loaded beam bends.
The deformation is exaggerated so its shape can be seen.
For a simply supported full-span UDL, .
Double L with w, E and I unchanged: δ becomes 16 times as large.
The readout uses , and .
Select the finish/support-specific limit from the original table.
Result and concise exam wording
Use the same mechanism: Balance the isolated beam. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.
Apply the reasoning to this section’s data and conditions
B1 characteristic reactions /=/.
B2 has three / points; end reactions /.
B3 central /=/ plus /.
Ultimate , , , .
Select UB S355, Class 1: , , .
The demonstrated checks pass.
Misconceptions and checks
Use the same mechanism: Follow one strip of floor. At fixed area load, twice the tributary width gives twice the line load. An end reaction remains a concentrated force.
Apply the reasoning to this section’s data and conditions
- Do not make floor pressure a beam UDL without multiplying by tributary width.
- Do not transfer a supported beam’s entire load to each end.
- Include B3’s directly supported slab strip once.
- Do not add self-weight already included by the problem.
How the method transfers to a new variant
Use the same mechanism: Find which plate buckles first. At fixed width, a thinner plate has a larger width-to-thickness ratio. Local buckling then becomes more restrictive.
Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.
Vertical bending can trigger sideways motion
A beam has enough local bending resistance. Check whether its compression flange can move sideways and twist.
Prediction, then explanation. Adding a valid lateral restraint shortens a stability segment. It need not change the beam’s vertical reaction or moment diagram.
Identify the compressed flange and effective restraints. Calculate the specified slenderness, read buckling strength and compare resistance with the segment demand.
LE and ry use the same length unit. pb uses N/mm²; Sx uses mm³; Mb uses N·mm. mLT is dimensionless.
Scope. Use the specified section class, effective-length branch and loading condition. Load height alone does not prove a destabilizing case.
Check and takeaway. Removing a lateral restraint requires a new segment stability check. The old shorter-segment result cannot establish the longer segment’s adequacy.
Apply the reasoning to this section’s data and conditions
- Identify the vertical supports, span, lateral restraints and individual load positions.
- Keep dead and imposed loads separate; form the required ultimate and serviceability cases.
- Find reactions and the maximum shear/moment by equilibrium, with units.
- Choose a section-table row, confirm thickness-dependent strength, and classify both flange and web.
Check shear and bending.
Add segment LTB where restraint is discrete.
- Complete the requested web and deflection checks; state the governing result and any missing data.
Prediction with explained answer
Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.
Apply the reasoning to this section’s data and conditions
Prediction and explained answer.
Invented variant: only the characteristic floor imposed pressure rises from to .
Find the revised B3 ultimate and , and imposed deflection; retain the original dead loading.
Answer and reasoning
All imposed effects multiply by .
B3 imposed point; imposed UDL.
;
Imposed deflection=
Maximum shear=; these checks still pass.
Mechanism detailsFollow the floor load in 3D
The complete mechanism is explained below.
Read each stage together with its stated conditions; playback and interaction are not required.
The floor carries pressure in .
The highlighted strip belongs to one secondary beam.
Multiply pressure by tributary width: .
The illustration uses .
- A primary beam receives the secondary beam reaction at their connection, not a new full-span UDL.
Trace reactions down to columns and foundations.
Count each loaded area once.