Beam example 1: fully restrained beam, from loads to deflection

Diagrams, explanations and answers are presented in reading order. No playback or response is required.

← Read this lecture example beside its chapter concepts

All answers shownChinese–English terminology
Diagrams, explanations and answers are presented in reading order. No playback or response is required.

Select a Grade S355 section for a fully laterally restrained, simply supported 7m beam. Check shear, bending, support web bearing, support web buckling and deflection. The central loads are 20kN dead and 60kN imposed; full-span UDLs are 7kNm dead and 35kNm imposed.

Original source: LectureNotes/Ch 3_Beam.pdf — p. 18, p. 19, p. 20, p. 21.

A given value comes from the question or diagram.

A lookup value comes from the named table.

A calculated value follows from the working.

Each assumption is stated where the calculation needs it.

Known information, diagram labels and unknowns

A safe beam can still sag too far

Check whether the beam displacement exceeds the permitted service limit.

The straight beam marks the unloaded position. The curved line and vertical arrow show downward displacement, exaggerated for explanation.
The straight beam marks the unloaded position. The curved line and vertical arrow show downward displacement, exaggerated for explanation.

Prediction, then explanation. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.

Load bends each beam segment. The curvature accumulates along the span. Material stiffness E and geometric stiffness I resist that deformation.

δmid=5wL4384EI\delta_{mid}=\frac{5wL^4}{384EI}

Use w in N/mm, L in mm, E in N/mm² and I in mm⁴. The resulting midspan deflection is in mm.

Scope. The formula assumes a prismatic, simply supported, linear-elastic beam with full-span UDL. Use the stated service load and deflection limit.

Check and takeaway. A higher yield grade does not automatically increase E. Passing a strength check therefore does not prove acceptable deflection.

Vertical bending can trigger sideways motion

A beam has enough local bending resistance. Check whether its compression flange can move sideways and twist.

The dashed straight line is the initial reference. The curved flange lines illustrate the labelled sideways movement and twist.
The dashed straight line is the initial reference. The curved flange lines illustrate the labelled sideways movement and twist.

Prediction, then explanation. Adding a valid lateral restraint shortens a stability segment. It need not change the beam’s vertical reaction or moment diagram.

Identify the compressed flange and effective restraints. Calculate the specified slenderness, read buckling strength and compare resistance with the segment demand.

λ=LE/ry,Mb=pbSx  (Class 1/2),mLTMmax≤Mb\lambda=L_E/r_y,\qquad M_b=p_bS_x\;\text{(Class 1/2)},\qquad m_{LT}M_{max}\le M_b

LE and ry use the same length unit. pb uses N/mm²; Sx uses mm³; Mb uses N·mm. mLT is dimensionless.

Scope. Use the specified section class, effective-length branch and loading condition. Load height alone does not prove a destabilizing case.

Check and takeaway. Removing a lateral restraint requires a new segment stability check. The old shorter-segment result cannot establish the longer segment’s adequacy.

Keep load categories separate

A floor carries permanent material and changing occupancy loads. Find the design load for the stated check.

The two boxes show G and Q with their separate factors. The plus sign joins their factored values.
The two boxes show G and Q with their separate factors. The plus sign joins their factored values.

Prediction, then explanation. Increasing imposed load changes its own term. It does not change the dead-load factor or the steel stiffness.

First convert mass to weight where required. Next collect G and Q in compatible units. Apply the combination specified by the course problem.

Wu=1.4G+1.6QW_u=1.4G+1.6Q

G is characteristic dead load; Q is characteristic imposed load. Wu is the design load for this course gravity combination.

Scope. This combination is not universal. Use the specified service load for deflection and the stated factors for other standards or cases.

Check and takeaway. Illustration: G = 10 kN and Q = 5 kN give 22 kN. Factoring their sum by one guessed factor loses the distinction.

Apply the reasoning to this section’s data and conditions

QuantityGiven, lookup or assumption
Span and loadingGiven in the upper drawing: L=3.5+3.5=7m, one central point load and two full-span UDL components.
Bearing

Given in the question: b1=160mm, ae=80mm, be=0.

Loaded flange is restrained against both specified local movements.

Lateral restraintGiven: compression flange fully restrained, so no member LTB check is needed.
Deflection

Lecturer assumes brittle finishes and uses unfactored imposed loads only; limit L360.

E=205,000Nmm2.

Section properties

Lookup Data File pp.9–10, row 533×210×82 UB.

Original solution also lists the values on p.19.

Why this method applies

Use the same mechanism: Vertical bending can trigger sideways motion. Adding a valid lateral restraint shortens a stability segment. It need not change the beam’s vertical reaction or moment diagram.

Balance the isolated beam

Find the two vertical reactions before calculating internal shear or moment.

A / RₐB / RᵦPaL
A and B are vertical supports. The downward load acts at distance a from A. Its distance from B is L − a.

Prediction, then explanation. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.

Take moments about A. Reaction A has zero lever arm there. Then use vertical force balance to find reaction A.

RBL=Pa,RA+RB=PR_B L=Pa,\qquad R_A+R_B=P

P, RA and RB are forces in kN. L is support spacing and a is load position, both in m.

Scope. These expressions describe one point load on a simply supported beam. Add other loads through equilibrium; keep their actual positions.

Check and takeaway. Illustration: P = 60 kN, L = 6 m and a = 2 m give RB = 20 kN and RA = 40 kN.

A table value has conditions

Find a design property without mixing a row, column or standard from a different case.

The row and column meet at one cell. The table heading supplies the units and the conditions that give the cell meaning.
The row and column meet at one cell. The table heading supplies the units and the conditions that give the cell meaning.

Prediction, then explanation. A different flange thickness can select a lower design strength even when the steel grade name remains unchanged.

Match the complete section designation. Read the relevant axis and unit. For strength tables, select material, thickness and curve before interpolating.

Given values come from the question. Lookup values come from a named table. Assumed values require an explicit condition.

Scope. A missing row or omitted restraint cannot be recovered from a schematic’s scale. Keep the result conditional when required data are absent.

Check and takeaway. Record the table, row, column and unit beside the substitution. That makes a later check possible.

Apply the reasoning to this section’s data and conditions

First distinguish applied load from internal action.

A load acts on the beam.

Shear V and moment M are internal actions needed to carry it.

Symmetry makes the two reactions equal.

The shear changes sign at the central point load.

Therefore, that is the maximum-moment position.

Full lateral restraint removes LTB from this example, but does not remove local web checks.

Select a trial section from its plastic modulus, then verify every other requirement.

1. Factor each load component

Use the same mechanism: Keep load categories separate. Increasing imposed load changes its own term. It does not change the dead-load factor or the steel stiffness.

Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.

Apply the reasoning to this section’s data and conditions

Physical interpretation: How a floor load reaches a beam

Each beam collects the load from its own strip of floor.

How a floor load reaches a beam — Each beam collects the load from its own strip of floor.

Sketch, not to scale; use the original dimensions.

  1. Find the tributary width from the actual plan.
  2. Area load × tributary width gives load per beam length.
  3. A supporting beam receives the other beam’s end reaction.

Remember: A reaction becomes a point load, not automatically a UDL.

Related concept and full method

P=1.4Gpoint+1.6Qpoint=1.4×20+1.6×60=28+96=124kNw=1.4g+1.6q=1.4×7+1.6×35=9.8+56=65.8kNm

The given dead UDL is the prescribed design input.

Do not add an extra assumed self-weight on top of it.

Keep the unfactored imposed loads 60kN and 35kNm for the separate deflection calculation.

Mechanism detailsFrom characteristic to design load2 concepts · 1 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. G is permanent load; Q is imposed load.

    A surface load and a line load also have different units.

  2. This illustration uses the course gravity case .

    Other combinations in the original text retain their own factors.

  3. For illustrative , the separate load contributions show what changes when Q increases.
  4. Do not carry this ULS total automatically into deflection.

    Follow the stated SLS load case.

2. Reactions, shear and maximum moment

Use the same mechanism: Balance the isolated beam. Move the same load toward B. Reaction B increases because the load has a larger moment arm about A.

A cut reveals the internal actions

Find where the beam moment is largest. A large load arrow alone does not locate that point.

The dashed imaginary cut separates two beam pieces. The opposing arrows represent the shear action between those pieces.
The dashed imaginary cut separates two beam pieces. The opposing arrows represent the shear action between those pieces.

Prediction, then explanation. Under a uniform downward load, shear falls steadily. Moment reaches a stationary value where shear becomes zero.

Balance the forces on the cut piece to get V. Balance their moments about the cut to get M. Evaluate each load region separately.

V(x)=RA−wx,M(x)=RAx−wx22V(x)=R_A-wx,\qquad M(x)=R_Ax-\frac{wx^2}{2}

x and L use m; w uses kN/m; V uses kN; M uses kN·m. These lines apply before any point load.

Scope. A point load adds a shear jump. A concentrated couple adds a moment jump. Check load points, supports and overhang roots too.

Check and takeaway. A UDL gives a sloping shear line and a curved moment line. A flat moment diagram therefore cannot represent a loaded UDL region.

Apply the reasoning to this section’s data and conditions

Total ultimate load: 124+65.8×7=584.6kNRA=RB=584.62=292.3kNImmediately left of midspan: V=292.3−65.8×3.5=62kNImmediately right of midspan: V=62−124=−62kNImmediately left of the right support: V=−62−65.8×3.5=−292.3kNMmid=RA×3.5−w×3.522=292.3×3.5−65.8×12.252=1,023.05−403.025=620.025kN·m

Equivalently PL4+wL28=124×74+65.8×498=217+403.025=620.025kN·m.

The source labels 620 after rounding.

UDL makes shear linear and bending parabolic.

The point load makes a shear jump of 124kN but no moment jump.

Mechanism detailsBalance reactions and moments2 concepts · 2 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. This demonstrator is a simply supported 6 m beam with a 60 kN point load.

    It is not the page’s original loading diagram.

  2. .

    Moving the load towards B increases .

  3. .

    The two upward reactions must sum to P.

  4. With the load at midspan, .

    End couples, UDLs and overhangs require their own equilibrium terms.

3. Select a trial section and read the correct columns

Use the same mechanism: A table value has conditions. A different flange thickness can select a lower design strength even when the steel grade name remains unchanged.

Apply the reasoning to this section’s data and conditions

Initially assume flange thickness T≤16mm and trial py=355Nmm2. Sx,required=Mpy=620.025×106355=1,746,549mm3=1,746.549cm3Trial 533×210×82 UB: Sx=2,059cm3>1,746.549.
Table columnSelected-row value
D; web t; flange T; root r; clear web d (mm)528.3;9.6;13.2;12.7;476.5
Flange bT; web dt7.91;49.6
Major-axis Ix; elastic Zx; plastic Sx47,540cm4;1,800cm3;2,059cm3

533 and 210 are nominal section designations, not the exact D and flange width.

The table’s T=13.2mm confirms the initial py=355 assumption.

Select the major-axis columns because the vertical load bends the beam about x–x.

This is the lecturer’s suitable trial section, not a demonstrated minimum-mass optimum.

Mechanism detailsRead a table without losing the keys1 concept · 4 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. Name the required property: material strength, section property, buckling strength or a moment factor.
  2. Keep section size, steel grade, thickness band, curve and axis as separate lookup keys.
  3. , and require different conversion powers.

    Do not use adjacent columns interchangeably.

  4. Use bracketing rows within the same valid column.

    The original page remains the source of all table values.

4. Establish the section class and web-shear branch

Find which plate buckles first

Before using plastic bending resistance, check whether the flange and web can sustain the required stress distribution.

The short waves are local plate buckling. They differ from sideways movement of the whole member.
The short waves are local plate buckling. They differ from sideways movement of the whole member.

Prediction, then explanation. At fixed width, a thinner plate has a larger width-to-thickness ratio. Local buckling then becomes more restrictive.

Calculate the flange and web ratios separately. Compare each with the limits for its stress condition. The worse class governs.

ε=275/py\varepsilon=\sqrt{275/p_y}

py is the design yield strength in N/mm². ε is a dimensionless scale used in the supplied classification limits.

Scope. Pure bending and uniform compression use different web limits. Class 2 allows plastic resistance but not the Class 1 rotation capability.

Check and takeaway. A Class 1 web and Class 2 flange give a Class 2 section. Do not average the class numbers.

The web carries the shear check

Compare the applied shear with the resistance of the prescribed shear area.

At the imaginary cut, opposing arrows resist relative sliding. The rolled-UB calculation below assigns the shear area to the web.
At the imaginary cut, opposing arrows resist relative sliding. The rolled-UB calculation below assigns the shear area to the web.

Prediction, then explanation. At fixed design strength and depth, increasing web thickness increases this shear resistance.

Calculate the prescribed shear area. Multiply by the design shear stress from the course rule. Then compare matching force units.

Av=Dt,Vc=pyAv/3A_v=Dt,\qquad V_c=p_yA_v/\sqrt{3}

D is overall depth; t is web thickness, in mm. Av uses mm². py uses N/mm², giving Vc in N.

Scope. Apply this area definition to the stated rolled section. Check web slenderness separately. The factor 0.6 is the low-shear threshold, not this resistance coefficient.

Check and takeaway. A shear pass alone does not prove bending, deflection or local support-web adequacy.

Apply the reasoning to this section’s data and conditions

Physical interpretation: A thin part can wrinkle first

A thin plate may wrinkle before the whole steel member reaches its intended resistance.

A thin part can wrinkle first — A thin plate may wrinkle before the whole steel member reaches its intended resistance.

Sketch, not to scale; use the original dimensions.

  1. Check flange and web slenderness using their own definitions.
  2. Compare each ratio with the correct class limits.
  3. The element with the more restrictive class determines the section class.

Remember: Bending limits and uniform-compression limits are different.

Related concept and full method

ε=275py=275355=0.880141Class 1 flange limit: 9ε=7.92127;bT=7.91≤7.92127Class 1 web limit in pure bending: 80ε=70.4113;dt=49.6≤70.4113Both elements are Class 1, giving a plastic section. Web shear-buckling threshold: 70ε=61.6099;dt=49.6<61.6099

The flange classification is close to its limit: use the table ratio and keep enough precision.

The web’s 80ε bending-class limit and 70ε shear-buckling threshold are different tests.

A separate shear-web-buckling calculation is not required; concentrated reaction web buckling is still checked below.

Mechanism detailsWhy thin elements buckle locally2 concepts · 1 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. The flange outstand and web have different widths, thicknesses and edge support conditions.
  2. A thinner plate can wrinkle locally before the complete member loses stability.
  3. Class 1 allows plastic rotation.

    Class 2 reaches plastic resistance.

    Class 3 reaches elastic resistance.

    Class 4 requires effective properties.

  4. Check every relevant compression element with the supplied limits and stress distribution.

    The deformation shown is qualitative.

5. Resist the largest shear

Use the same mechanism: The web carries the shear check. At fixed design strength and depth, increasing web thickness increases this shear resistance.

Apply the reasoning to this section’s data and conditions

Av=tD=9.6×528.3=5,071.68mm2Vc=pyAv3=355×5,071.683=1,039,488N=1,039.488kNVmax=292.3kN<1,039.488kNPasses.

Mechanism detailsSee shear in the web1 concept · 1 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. Internal shear keeps the two sides of the cut in vertical equilibrium.
  2. For the course’s common I-section case, the web provides the principal shear area.

    Use the specified definition.

  3. A slender web may require a different shear-buckling route before a simple shear-resistance formula is used.
  4. Use where applicable in the course.

    Convert N to kN before comparing with design shear.

6. Check coexistent shear, then bending

Internal tension and compression resist moment

Find which section resistance applies before comparing it with the moment demand.

In sagging bending, the upper region compresses and the lower region stretches. Together their forces form a resisting couple.
In sagging bending, the upper region compresses and the lower region stretches. Together their forces form a resisting couple.

Prediction, then explanation. A larger appropriate section modulus raises resistance at fixed strength. Local plate buckling can restrict the usable modulus.

Classify the section first. At low shear, use the elastic expression for Class 3 or the prescribed capped plastic expression for Classes 1 and 2.

Mc=min⁡(pyS,1.2pyZ)for Class 1/2 at low shearM_c=\min(p_yS,1.2p_yZ)\quad\text{for Class 1/2 at low shear}

py uses N/mm². S is plastic modulus and Z is elastic modulus, both in mm³. Mc then uses N·mm.

Scope. This is section resistance, not whole-member LTB resistance. High shear and Class 4 require their appropriate treatment.

Check and takeaway. Selecting the larger of the two capped terms defeats the cap. Use their minimum.

Shear and bending share the web

Decide whether the unreduced bending resistance remains applicable at the section being checked.

The same web region participates in shear and longitudinal bending stress. The two demands must be evaluated at one section.
The same web region participates in shear and longitudinal bending stress. The two demands must be evaluated at one section.

Prediction, then explanation. Raising shear beyond the specified threshold can reduce available bending resistance. A distant maximum shear is not the coexistent shear.

Find the moment-check position. Evaluate the shear there. Compare it with the low-shear threshold before selecting the resistance expression.

V≤0.6Vcis the course low-shear conditionV\le0.6V_c\quad\text{is the course low-shear condition}

V is shear at the checked section; Vc is its shear resistance. Both use the same force unit.

Scope. Above the threshold, use the supplied reduction expression. The threshold itself is not a substitute resistance formula.

Check and takeaway. If the maximum shear anywhere is below the threshold, all sections satisfy that low-shear condition. Otherwise check the actual positions.

Apply the reasoning to this section’s data and conditions

At the maximum-moment section, |V|=62kN. 0.6Vc=0.6×1,039.488=623.693kN62<623.693; the low-shear bending formula applies.pySx=355×2,059×103106=730.945kN·m1.2pyZx=1.2×355×1,800×103106=766.8kN·mMc=min(730.945,766.8)=730.945kN·m620.025<730.945: bending passes.

The largest shear actually also lies below 0.6Vc, so every section is low-shear here.

Do not use the larger of the two moment resistances: the second is a ceiling.

Mechanism detailsCompression and tension across a section2 concepts · 1 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. For sagging, the top flange is in compression and the bottom in tension; hogging reverses this.
  2. Elastic bending stress varies with distance from the neutral axis: .
  3. The section class governs whether elastic, plastic or effective properties may be used.
  4. Use the shear at the section under examination.

    The largest shear elsewhere is not automatically coexistent.

7. Support web bearing

A concentrated force spreads into the web

Check local web resistance at a support or concentrated load, even if overall beam strength passes.

Compare Narrow contact with Wide contact. Both receive the same force, but the wider contact distributes it over a longer region.
Compare Narrow contact with Wide contact. Both receive the same force, but the wider contact distributes it over a longer region.

Prediction, then explanation. A longer valid stiff-bearing length can spread the same force over more web. A flexible contact is not automatically stiff bearing.

Match the actual bearing geometry to its source sketch. Use that sketch’s dimensions and permitted spread to calculate the resisting region.

b₁ is stiff-bearing length in mm. Web thickness and applicable design strength enter the prescribed local resistance equation.

Scope. End and interior cases can differ. A lateral-restraint symbol does not provide a bearing length or a load-introduction detail.

Check and takeaway. If bearing geometry is missing, give the applicable symbolic check and state the missing input. Do not borrow another example’s dimensions.

Apply the reasoning to this section’s data and conditions

Physical interpretation: A concentrated force can hurt one small region

A narrow contact presses much harder locally than the same force spread over a wider contact.

A concentrated force can hurt one small region — A narrow contact presses much harder locally than the same force spread over a wider contact.

Sketch, not to scale; use the original dimensions.

  1. Find the actual stiff bearing length and end position.
  2. Check local crushing and local web buckling separately.
  3. Use the restraint conditions required by each expression.

Remember: Missing contact dimensions cannot be guessed from drawing scale.

Related concept and full method

k=T+r=13.2+12.7=25.9mmn=min(2+0.6bek,5)=min(2+0,5)=2b1+nk=160+2×25.9=211.8mmPbw=(b1+nk)tpyw=211.8×9.6×355=721,814.4N=721.8144kN721.8144>292.3: support bearing passes.

Web thickness 9.6mm also gives pyw=355.

This is an end bearing, hence n=2 with be=0; using the interior value 5 would artificially increase resistance.

Mechanism detailsSpread a concentrated force into the web1 concept · 4 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. A concentrated reaction first enters through the bearing/contact region.
  2. The flange and root geometry spread the force before it enters the web.
  3. A wider effective bearing region can reduce local stress for the same force.
  4. End distance, stiff bearing length and restraint conditions must come from the original question.

    The illustrated dimensions explain the mechanism.

    They do not replace the original question data.

8. Support web buckling

The loaded web can act as a short strut

A concentrated load can buckle the web instead of crushing it. This requires a separate local check.

Local bowWebFlangeExaggerated
The compressed strip lies below the load. Its possible lateral bow differs from whole-beam lateral-torsional buckling.

Prediction, then explanation. Reduced local restraint can increase the relevant effective length and reduce local buckling resistance.

First calculate the source model’s effective strip and base resistance. Then apply the branch required by local restraint and load position.

Local web effective length is not the beam span or the LTB segment length. Use the symbol definition in the selected local formula.

Scope. The short-strut picture explains a mechanism; it is not a derivation of every coefficient in the supplied web rule.

Check and takeaway. A local bearing pass does not establish a local buckling pass. State both conclusions and any unresolved restraint condition.

Apply the reasoning to this section’s data and conditions

0.7d=0.7×476.5=333.55mmae=80mm<333.55mm; use the end-reduced branch. End factor: 80+333.551.4×476.5=413.55667.1=0.619922Web factor: 25×0.880141×9.6211.8×476.5=211.2338100,922.7≈0.664919Px=[413.55667.1]×[211.2338100,922.7]×721.8144=297.531kN>292.3kNPasses, but with a small margin.

Both local flange restraints are explicitly given, so no Pxr reduction is needed.

The reaction uses 98.24% of this resistance: support web buckling is the tightest strength check.

Keep the given ae and be distinct.

Mechanism detailsThe web behaves like a short strut1 concept · 1 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. A concentrated force compresses a local region between the flanges.
  2. The thin web can buckle sideways before local crushing governs.
  3. The source distinguishes restraint against rotation and relative lateral movement.
  4. Web bearing and web buckling are separate checks.

    Select the original expression whose assumptions are satisfied.

9. Deflection under the specified serviceability case

Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.

Apply the reasoning to this section’s data and conditions

Physical interpretation: How much does the beam sag?

Strength asks whether it fails; deflection asks how far it moves.

How much does the beam sag? — Strength asks whether it fails; deflection asks how far it moves.

Sketch, not to scale; use the original dimensions.

  1. Use the serviceability load case specified by the course question.
  2. Choose the expression matching the support and load positions.
  3. Use consistent units for load, length, E and I.

Remember: The largest deflection is not always at midspan.

Related concept and full method

Pservice=60kN=60,000N;wservice=35kNm=35NmmL=7,000mm;Ix=47,540×104=475,400,000mm4δP=PL348EI=60,000×7,000348×205,000×475,400,000=4.39938mmδw=5wL4384EI=5×35×7,0004384×205,000×475,400,000=11.22757mmδtotal=4.39938+11.22757=15.62695mmLimit: L360=7,000360=19.44444mm15.62695<19.44444: passes under the assumed brittle-finish condition.

Symmetry puts the maximum at midspan for both components, so adding these two maximum values is valid.

The selected 533×210×82 UB passes all requested checks under the stated model.

Mechanism detailsSee stiffness and deflection1 concept · 1 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. Use the specified SLS load, span and support arrangement.

    The demonstrator has a full-span UDL.

  2. The loaded beam bends.

    The deformation is exaggerated so its shape can be seen.

  3. For a simply supported full-span UDL, .

    Double L with w, E and I unchanged: δ becomes 16 times as large.

  4. The readout uses , and .

    Select the finish/support-specific limit from the original table.

Result and concise exam wording

Use the same mechanism: The loaded web can act as a short strut. Reduced local restraint can increase the relevant effective length and reduce local buckling resistance.

Apply the reasoning to this section’s data and conditions

Use S355 533×210×82 UB, Class 1.

Ultimate P=124kN, w=65.8kNm, R=Vmax=292.3kN, Mmax=620.025kN·m.

Vc=1,039.49kN.

Mc=min(730.945,766.8)=730.945kN·m.

Pbw=721.814kN; Px=297.531kN>292.3.

Imposed-load δ=15.627mm<L360=19.444mm.

Adequate; support web buckling is the closest strength check.

Misconceptions and checks

Use the same mechanism: The loaded web can act as a short strut. Reduced local restraint can increase the relevant effective length and reduce local buckling resistance.

Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.

Use the same mechanism: Vertical bending can trigger sideways motion. Adding a valid lateral restraint shortens a stability segment. It need not change the beam’s vertical reaction or moment diagram.

Apply the reasoning to this section’s data and conditions

  • Do not factor imposed loads again in the prescribed deflection check.
  • Use actual table dimensions, not 533mm as D.
  • Compare against the smaller moment-capacity expression.
  • Do not confuse shear-web slenderness with concentrated-load web buckling.

How the method transfers to a new variant

Use the same mechanism: Find which plate buckles first. At fixed width, a thinner plate has a larger width-to-thickness ratio. Local buckling then becomes more restrictive.

Use the same mechanism: A safe beam can still sag too far. For the same UDL and stiffness, doubling span multiplies deflection by sixteen. Doubling I halves deflection.

Use the same mechanism: Vertical bending can trigger sideways motion. Adding a valid lateral restraint shortens a stability segment. It need not change the beam’s vertical reaction or moment diagram.

Apply the reasoning to this section’s data and conditions

  1. Identify the vertical supports, span, lateral restraints and individual load positions.
  2. Keep dead and imposed loads separate; form the required ultimate and serviceability cases.
  3. Find reactions and the maximum shear/moment by equilibrium, with units.
  4. Choose a section-table row, confirm thickness-dependent strength, and classify both flange and web.
  5. Check shear and bending.

    Add segment LTB where restraint is discrete.

  6. Complete the requested web and deflection checks; state the governing result and any missing data.

Prediction with explained answer

Use the same mechanism: The loaded web can act as a short strut. Reduced local restraint can increase the relevant effective length and reduce local buckling resistance.

Use the same mechanism: A concentrated force spreads into the web. A longer valid stiff-bearing length can spread the same force over more web. A flexible contact is not automatically stiff bearing.

Use the same mechanism: Vertical bending can trigger sideways motion. Adding a valid lateral restraint shortens a stability segment. It need not change the beam’s vertical reaction or moment diagram.

Apply the reasoning to this section’s data and conditions

Prediction and explained answer.

Invented variant: keep the section and ultimate loads, but reduce the stiff bearing to 140mm, centred at the member end (ae=70mm, be=0).

Is the support web still adequate?

Hint

The change affects both the bearing resistance and the end-reduction factor.

Answer and reasoning

Recalculate n=2 and b1+nk=191.8mm.

Pbw=191.8×9.6×3551,000=653.6544kN

Px=[70+333.55667.1]×[25×275355×9.6191.8×476.5]×653.6544≈276.3kN, below 292.3kN.

Bearing passes but web buckling fails.

The original section conclusion cannot simply be reused.

Mechanism detailsSpread a concentrated force into the web2 concepts · 4 source expressions

The complete mechanism is explained below.

Read each stage together with its stated conditions; playback and interaction are not required.

  1. A concentrated reaction first enters through the bearing/contact region.
  2. The flange and root geometry spread the force before it enters the web.
  3. A wider effective bearing region can reduce local stress for the same force.
  4. End distance, stiff bearing length and restraint conditions must come from the original question.

    The illustrated dimensions explain the mechanism.

    They do not replace the original question data.